degrees of protection IP (International Protection)

1° number 2° number added letter additional letter
0...1 0...8 A...D H...W

1° NUMBER
protection against the contact of external solid bodies and against the access to dangerous parts

numb. protection of the material protection of the persons
0 not protect  
1 protected against solid bodies of superior dimensions to 50 mm. protect against the access with the back of the hand
2 protected against solid bodies of superior dimensions to 12 mm. protect against the access with a finger
3 protected against solid bodies of superior dimensions to 2.5 mm. protect against the access with a tool
4 protected against solid bodies of superior dimensions to 1 mm. protect against the access with a wire
5 protect against the powder protect against the access with a wire
6 totally protect against the powder protect against the access with a wire

2° NUMBER
protection against the penetration of the liquids

numb. protection of the material
0 not protect
1 protect against the vertical fall of water drops
2 protect against the fall of water drops with inclination max of 15°
3 protect against the rain
4 protect against the water sprays
5 protect against water jets
6 protect against big waves
7 protect against the effects of the immersion
8 protected against the effects of the submersion

added letter
(optional) (a)

lett. protection of the persons
A protect against the access with the back of the hand
B protect against the access with a finger
C protect against the access with a tool
D protect against the access with a wire

(a) only used if:
the real protection against agreed to dangerous births is superior to the suitable one from the first number;
the protection against the access to dangerous parts is only indicated and before the figure comes therefore replaced from one x;

additional letter
(optional)

lett. protection of the material
H equipment to high tension
M tried against the harmful due effects to the entry of the water with in operation apparatus
S tried against the harmful due effects to the entry of the water with apparatus not in operation
W adapted to the use in specified atmospheric conditions